Operating Procedures
Communication Cycle
Time
Internal transceiver error
Lit when an error occurs during a transceiver test. Clear the error by resetting
the Unit. If this is a recurring error, replace the Unit.
Transceiver error
Lit when an error occurs at the transceiver.
Clear the error by resetting the Unit.
If this is a recurring error, replace the Unit.
EEPROM error
Lit when an error occurs in the EEPROM.
An error may recur in a Unit if there is a faulty network configuration. Recheck
the settings.
If the error recurs after rechecking the settings, replace the Unit.
The network status is shown.
Token hold node number
Displays the node number of the node where the token is held when the
Upload Button is clicked.
Allowed min. frame interval
Displays the minimum allowable frame interval for the network in which the
specified Unit is participating.
Refresh cycle time
Displays the allowable refresh cycle time for the specified Unit.
Measure time
Displays the current value, maximum value, and minimum value of the mea-
sured refresh cycle time for the specified Unit.
Section 11-2
183