Sends a request message Word Block Data Write.
The remote node address specified in the control data of the CMND(490)
instruction is used as the write destination node number. The FINS command
can be executed from the CPU Unit of the FL-net Unit, but an error will occur if
the command passes through a FINS network on another layer.
1. This command is provided to ensure compatibility with applications creat-
ed with the CS1W-FLN01.
2. Use WORD BLOCK DATA READ/WRITE with specified node numbers to
create new applications.
29
04
Command
First address of the
code
virtual address space
29
04
Command
Completion
code
code
Set the first address where data will be written using hexadecimal format.
Addresses spanning multiple areas cannot be set.
Refer to 7-4 CS/CJ-series Memory Areas and Virtual Addresses if the node
where data will be written is an OMRON FL-net Unit. If it is another manufac-
turer's FL-net node however, refer to the manual for that node.
Specifies up to 512 words for the number of words in data that is sent.
Response code
0000
Normal completion
0101
Local node not part of network
0104
Reception buffer overflow, queuing not started (reception side)
0107
Unit's internal buffer full
0205
No response from remote node
1001
Command length too long
1002
Insufficient command length
1005
Sequence number error, sequence version error
110C
Source node is local node, requested number of words is
greater than 512.
2605
Servicing in progress
0 to 1,024 bytes (512 words)
Data that is written
Size
Description