Allocated Words - Omron CS1W-FLN22 Operation Manual

100base-tx, sysmac cs / cj series, fl-net units
Table of Contents

Advertisement

Allocated Words

4-1
Allocated Words
CPU Bus Unit System Setup
(Set using CX-FLnet or
FL-net Unit Support Software.)
Allocated Words in CIO Area for
n = CIO 1500 + 25 x unit number
n + 1
n + 24
Allocated Words in DM Area for
n = D30000 + 100 x unit number
m + 1
m + 99
48
The FL-net Unit is allocated words in the following four areas for reading set-
tings and status.
• System Setup for CPU Bus Units
Stores initial setup for the FL-net node.
• System Setup in FL-net Unit
Stores Data Link data when the FL-net Unit's Data Link function is used
with the Unit built-in method.
• Allocated Words in the CIO Area
Stores software switches and status information for functions.
• Allocated Words in the DM Area
Stores software switch and status information for functions.
CPU Unit
to
CPU Bus Units
15
0
n
to
CPU Bus Units
15
0
m
to
The words in the CIO Area and DM Area are allocated according to the unit
number as shown in the following tables. The 25 words are allocated per Unit
in the CIO Area and 100 word are allocated per Unit in the DM Area.
Transferred
when power
supply is turned
ON or Unit is
restarted.
System Setup in FL-net Unit
(Set using CX-FLnet or
FL-net Unit Support Software.)
15
I/O refresh
15
I/O refresh
Section 4-1
FL-net Unit
to
to
0
to
0
to

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cj1w-fln22

Table of Contents