Appendix F
FL-net Unit Support Software Ver. 1.6
Monitor (Unit Status)
Shows the status of the FL-net Unit.
The status shown here is the same as the Unit status which is reflected in the CIO Area.
FA Link active
Lit when FA Link operation is normal.
Received message
Lit when a transparent message is received.
Power supplied
Lit when transceiver power supply is normal.
FA Link Area mapping error
Lit when FA Link Area mapping is incorrect. Recheck the settings.
Token watchdog timer set error
Lit when time for monitoring token in network is incorrect.
This error occurs for reasons such as faulty network configuration.
Restore by resetting the Unit.
IP address set error
Lit when IP address setting is incorrect. Recheck the setting.
Internal transceiver error
Lit when an error occurs during a transceiver test. Restore by resetting the Unit.
If this is a recurring error, replace the Unit.
Transceiver error
Lit when an error occurs at the transceiver.
Restore by resetting the Unit.
If this is a recurring error, replace the Unit.
EEPROM error
Lit when an error occurs at the EEPROM.
There are cases in which an error recurs in a Unit in a faulty network configuration.
Recheck the settings.
If the error recurs after rechecking the settings, replace the Unit.