Inspections
Changing the IP Address Setting Method
1,2,3...
3. Turn OFF the power to the PLC, remove the CS1W-FLN12, and install the
CS1W-FLN22.
4. Turn ON the power to the PLC and check that the RUN indicator on the
CS1W-FLN22 is lit.
5. Write the data that was read using the CX-FLnet or FL-net Unit Support
Software. Select System setting and Unit area setting, and then click the
Write Button in each of the dialog boxes to write the settings.
6. Restart the CS1W-FLN22 or cycle the PLC power to enable the new set-
tings. Make sure that the RUN indicator on the CS1W-FLN22 is lit.
The IP address setting method must be changed to either the default setting
(192.168.250 + node No.) or Setup area if the IP address for the CS1W-
FLN12 was set using the rotary switch on the rear of the Unit. Use the follow-
ing procedure to change the IP address setting method.
1. From the CX-FLnet or FL-net Unit Support Software, read the settings from
the CS1W-FLN12.
Check whether the IP address setting method is set to Unit rear rotary SW
+ node No. or Unit rear rotary SW.
2. Turn OFF the power to the PLC, remove the CS1W-FLN12, and confirm
the IP address of the corresponding node from the settings for the IP ad-
dress setting rotary switch on the rear of the Unit and the node address
setting switch on the front of the Unit.