Troubleshooting Procedures; Startup Problems - Omron CS1W-FLN22 Operation Manual

100base-tx, sysmac cs / cj series, fl-net units
Table of Contents

Advertisement

Troubleshooting Procedures

Error
Meaning
code
0300
Parameter error; packet discarded Commands
0601
CPU Bus Unit error
0602
CPU Bus Unit memory error
Note
10-4 Troubleshooting Procedures

10-4-1 Startup Problems

RUN
HER
PER
P/S
Not lit Not lit Not lit Not lit Power is not being supplied to the CPU Unit
Not lit ---
Lit
---
Not lit Lit
---
---
152
Detailed error code
1st byte
Bit 15:
Bits 08 to 14: SNA
Bits 00 to 07: SA1
Responses
Bit 15:
Bits 08 to 14: DNA
Bits 00 to 07: DA1
Arbitrary
01: Read
error
02: Write
error
1. The time information in the CPU Unit is used in the CPU Bus Units.
2. If the time information cannot be read from the CPU Unit, the time stamp
in the error log will be all zeros. This can occur due to CPU Unit startup
error, unit number errors, CPU error, and model number errors. If the time
is read out from a Programming Device, the time will be shown as all zeros
in the year 2000.
3. The battery must be installed in the CS-series CPU Unit, the power turned
ON, and then the time set before the clock in the CPU Unit can be used.
The time will not be set correctly in the error log unless the clock time is set
correctly.
4. An error record is not created in EEPROM when a CPU Bus Unit memory
error occurs.
The following procedures can be used to troubleshoot various problems in
system operation.
Probable cause
or the power supply voltage is too low.
The mounting screws on the FL-net Unit
are loose.
An error occurred in the FL-net Unit.
The same unit number is being used on
another Unit as well.
The FL-net Unit is not registered in an I/O
table.
The node address is set outside the range. Set the node number to between 01 and F9
An error occurred in the FL-net Unit.
2nd byte
Check the command format and
OFF
set the correct command data.
ON
Restart the CPU Unit. If the prob-
lem persists, replace the FL-net
(Ver. 2.00) Unit.
06: Error log
Restart the CPU Unit. If the prob-
lem persists, replace the FL-net
(Ver. 2.00) Unit.
Supply power.
Make sure that the correct voltage is being
supplied.
Tighten the screws on the FL-net Unit.
Restart the PLC. If the problem persists,
replace the FL-net Unit.
Correct the unit number setting and restart
the PLC.
Use a CX-Programmer or Programming
Console to create a new I/O table.
Hex and restart the PLC.
Restart the PLC. If the problem persists,
replace the FL-net Unit.
Section 10-4
Correction
PROM
---
Saved
Saved
(except
for error
log)
Correction
EE-