Connecting And Using A Peripheral Device For The Plc - Omron CS1W-FLN22 Operation Manual

100base-tx, sysmac cs / cj series, fl-net units
Table of Contents

Advertisement

Creating Routing Tables
PLC #1 (local node)
Node #1
PLC #1
relay network table
End
Relay
network
network
To go to network #3,
first go to node #3 at
network #1.
3-9-2

Connecting and Using a Peripheral Device for the PLC

42
The following example shows a routing table for sending data from PLC #1
(the local node: network address 1, node number 1) to PLC #4 (the destina-
tion node: network address 3, node number 2).
PLC #2 (relay node)
Node #2
Network #1
PLC #2
relay network table
End
Relay
Relay
Relay
network
network
node
node
To go to network #3,
first go to node #2 at
network #2.
Note In the above example, the routing tables required to send a message in one
direction from PLC #1 to PLC #4 are shown. Similar settings would need to be
added to the routing tables to enable sending a message the other direction,
i.e., from PLC #1 to PLC #4.
Routing tables must be created by a CX-Integrator connected to the PLC.
(They cannot be created using a Programming Console.) For details on how
to connect and use a CX-Integrator, refer to the CX-Integrator User's Manual.
Note
1. When routing tables are transferred from the CX-Integrator to a PLC, the
CPU Bus Unit will be reset so that the set routing tables can be read and
enabled. Make sure that the equipment will not be adversely affected when
the CPU Bus Unit is reset before transferring the routing tables.
2. To transfer routing tables for multiple nodes to a PLC in one batch, connect
the CX-Integrator to a PLC with only one Communications Unit mounted.
Routing tables cannot be transferred to other nodes from a PLC with mul-
tiple Communications Units mounted.
3. Routing tables can only be transferred as a batch to multiple nodes within
the same network as the PLC to which the CX-Integrator is connected.
Node #2
PLC #3
Unit #0
(relay node)
Node #1
Unit #1
Node #3
Node #1
Network #2
Network #3
End network
PLC #3
relay network table
Local
Unit
network
number
address
(To go to network #3
according to the local
network table, go
through the unit
number of the local
CPU Rack.)
Section 3-9
PLC #4 (destination node)
Node #2
(The network is the same,
so go to node #2 at network #3.)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cj1w-fln22

Table of Contents