Command/Response Reference
Precautions
Response Codes
7-5-5

TRANSPARENT MESSAGE SEND

Command Block
Response Block
Parameters
FA Message Header
(Command)
FA Message Data
(Command)
Precautions
Response Codes
112
Error Code, Detailed Information
Details of the error stored in the record. Refer to 10-3-2 Error Log Error Codes
for details.
Minute, Second, Day, Hour, Year, Month
Indicate the time at which the error stored in the record occurred.
If the error log contains fewer records than the number specified in the num-
ber of records parameter, all records stored in the error log at the time the
command is executed will be returned and the command executed will end
normally.
Response code
0000
Normal
1001
Command too large
1002
Command too small
1103
Beginning record number is out of range
110C
The number of read records is 0.
Sends a transparent message frame (transaction codes 00000 to 59999).
29
01
64 bytes
Command
FA message
code
header
29
01
Command
Completion
code
code
FA message header for the transparent message frame being sent.
FA message data of the transparent message frame being sent. Refer to the
following pages for details.
If this command is executed for a receiving node before the transparent mes-
sage previously received by the corresponding node has been read by the
TRANSPARENT MESSAGE RECEIVE FRAME READ (29 02) command, an
error will occur (response code 0x0104: Reception buffer overflow).
Response code
0000
Normal completion
0101
Local node not part of network.
0104
Reception buffer overflow, queuing not started (reception
side).
0107
Unit's internal buffer is full.
0205
No response from remote node
1001
Command length too long
1002
Insufficient command length
Description