Command/Response Reference
Response
Execute
condition
0000
A202
00
00
(Continued next page.)
+4:
+5:
D02000
+0
+1
• Sends a transparent frame just once when the Network
Communications Port Enabled Flag for port 0 and the
execute condition (CIO 000000) turn ON.
• Creates control data starting at D00000.
Word
@MOV(21)
D00000
# 004C
D00001
D00000
D00002
@MOV(21)
D00003
# 0004
D00001
D00004
@MOV(21)
# 0000
D00005
D00002
@MOV(21)
# 0010
D00003
@MOV(21)
# 0002
D00004
@MOV(21)
# 0000
D00005
to the unit number +
10 Hex.
0000 Hex
Response required,
communication port no. = 0,
number of retries = 0
0000 Hex
Response monitoring time
(default: 2 s)
:2901 Hex
:0000 Hex
Response code
(completed normally)
Content
Meaning
00
4C
Command data length: 76 bytes
00
04
Response data length: 4 bytes
00
00
Destination network address = 0
00
10
Destination node address = 0
Destination unit address = 10 Hex
00
02
Response required
Communications port No. = 0
Retries: 2
00
00
Response Monitoring Time = 2 s
Section 7-5