FL-net
Number of Connectable
Nodes and Node Numbers
Note
Network address
Node number
Data Communications
Cyclic transmission
Transmission Cycle
18
Up to 254 nodes can be connected to an FL-net network. Each node is
assigned a node number from 1 to 254.
Node number
1 to 249
Used for standard FL-net devices.
250 to 254
Used for FL-net maintenance purposes.
255
Reserved for the internal system use. (See notes 1 and 2.)
0
Reserved for internal system use. (See note 1.)
1. Not available to users.
2. Used for broadcasting.
192.
192.
168.
168.
250.
250.
1
2
Node number: 1 to 249 (for users)
FL-net supports data communications by cyclic transmission and message
transmission.
Cyclic data with token
With cyclic communications, the Common Memory is refreshed on a fixed
cycle time. Message communications are controlled so that the Common
Memory refresh time does not exceed the allowable refresh cycle time.
Each node constantly monitors the message communications frames that
travel through the network from the time it receives one local-node-directed
token until it receives the next local-node-directed token. When no message
communications frame travels through the network in a single cycle, 120% of
the cycle time value becomes the allowable refresh cycle time. In this way the
allowable refresh cycle time is actively determined according to the number of
nodes in the network.
Applications
FL-net
192.
192.
192.
168.
168.
168.
250.
250.
250.
248
249
250
Node number: 250 to 254
(for maintenance)
Cyclic transmission + message transmission
Section 2-1
192.
168.
250.
254
Message data