Inspections - Omron CS1W-FLN22 Operation Manual

100base-tx, sysmac cs / cj series, fl-net units
Table of Contents

Advertisement

Inspections

10-6 Inspections
Items
Inspection Interval
Inspection Items
Tools Required for Inspection
Standard Tools
Tools Required Under
Special Circumstances
Replacing CS1W-FLN12 with CS1W-FLN22
1,2,3...
162
Perform regular inspections to ensure that the FL-net Unit is functioning to its
optimum capacity.
Most of the parts that make up an FL-net Unit are semiconductor compo-
nents. None of the parts in the Unit will wear out after a specific lifetime, but
some parts may deteriorate due to extreme operating conditions. Therefore, it
is important to inspect the Unit regularly.
Normally inspect once or twice per year. Choose the inspection period
according to the severity of the operating conditions. New installation should
be inspected more frequently until they are judged to be stable.
Correct any of the items in the table below not conforming to the specified
standard
Item
Environment
Temperature around Unit
Humidity around Unit
Accumulated dust
Mounting
FL-net Unit firmly attached
Transceiver cable connector fully
pushed in
Condition of transceiver cable
Twisted-pair cable connector fully
pushed in
Condition of twisted-pair cable
The following tools are needed to inspect the FL-net Unit:
• Flat-blade and Phillips screwdrivers
• Tester or digital voltmeter
• Industrial alcohol and a clean cloth
• Synchroscope
• Pen oscilloscope
• Thermometer and hygrometer
Use the following procedure to replace CS1W-FLN12 with CS1W-FLN22.
1. Read the CS1W-FLN12 settings using the CX-FLnet or FL-net Unit Sup-
port Software.
Note The IP address setting method must be changed in the system settings if it is
set to use either the rotary switch on the rear of the Unit or the rotary switch
on the rear of the Unit + the node number. Refer to the following information
under Changing the IP Address Setting Method.
2. Set the hardware switches of the new CS1W-FLN22 to the same values as
the CS1W-FLN12 being replaced. Use the rotary switches on the front of
the Unit to make these settings.
• Unit number setting rotary switch
• Node address setting rotary switch
Details
0 to 55°C
10% to 90% (with no con-
densation)
No accumulated dust
No looseness
No looseness
No visible abnormality
No looseness
No visible abnormality
Section 10-6
Standard