Error Log
Error
Meaning
code
0103
Resend count exceeded (send
failed)
0105
Node address setting error (send
failed)
0107
Remote node not in network (send
failed)
0108
No Unit with specified unit
address (send failed)
010B
CPU Unit error (send failed)
010D
Destination address not in routing
tables (send failed)
010E
No routing table entry (send
failed)
010F
Routing table error (send failed)
0110
Too many relay points (send
failed)
0111
Command too long (send failed)
0112
Header error (send failed)
0117
Internal buffers full; packet dis-
carded
0118
Illegal packet discarded
0119
Local node busy (send failed)
0120
Unexpected routing error
0121
No setting in IP address table;
packet discarded
0122
Service not supported in current
mode; packet discarded
0123
Internal send buffer full; packet
discarded
0124
Maximum frame size exceeded;
routing failed
021A
Logic error in setting table
Detailed error code
1st byte
2nd byte
Commands
Bit 15:
OFF
Bits 08 to 14: SNA
Bits 00 to 07: SA1
Responses
Bit 15:
ON
Bits 08 to 14: DNA
Bits 00 to 07: DA1
00
01: Data link
table
02: Network
parameters
03: Routing
tables
04: Setup
05: CPU Bus
Unit Words
(CIO/DM)
Correction
Check transceiver at remote node. ---
Set the IP address correctly.
Check the connection to the
remote node.
Check the unit address at the
remote node.
Troubleshoot the error in the CPU
Unit using the PLC operation
manual.
Set the destination address in the
routing tables.
Set the local node, remote node,
and relay nodes in the routing
tables.
Create the routing tables correctly. ---
Reconstruct the network or cor-
rect the routing tables so that
commands are sent to within a 3-
level network range.
Check the command format and
set the correct command data.
Check the command format and
set the correct command data.
Change the network so that traffic
is not concentrated.
Check for nodes sending illegal
packets.
Change the network so that traffic
is not concentrated.
Check the routing tables.
Set the remote node in the IP
address table.
Select the IP address table or
both methods for the address con-
version method.
Change the network so that traffic
is not concentrated.
Reduce the size of the FINS mes-
sage.
Recreate the data specified by the
2nd byte of the detailed error
code.
Section 10-3
EE-
PROM
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
Saved
151

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cj1w-fln22