Omron CS1W-FLN22 Operation Manual page 126

100base-tx, sysmac cs / cj series, fl-net units
Table of Contents

Advertisement

Sending Commands from a PLC
Execution
condition
Reset B
Local Node Network
Participation Flag
Execution
condition
Reset D
Communications Flags
100
Communications
Port Enabled Flag
KEEP(011) A
Remote Node Network
Participation Flag
Operand,
control data
created with
@MOV and
@XFER.
Communications
instructions
@SEND
@RECV
@CMND
Communications
Port Enabled Flag
DIFU(013) B
Communications
Port Error Flag
Communications
Port Enabled Flag
KEEP(011) C
(Continued in same way.)
The execution status of the SEND(090), RECV(098), and CMND(490) instruc-
tions is always reflected by the communications flags (i.e., the Communica-
tions Port Enabled Flag and the Communications Port Error Flag). The CS-
series CPU Unit's communications flags are allocated in the Auxiliary Area as
shown in the following table.
Flag name
Communications Port
Enabled Flag
Communications Port
Error Flag
Note With CS/CJ-series PLCs, communications ports 0 to 7 are also used for exe-
cuting the PLCMR(260) (PROTOCOL MACRO) instruction, so these flags are
used in common for SEND(090), RECV(098), CMND(490), and PLCMR(260).
While PLCMR(260) is being executed, SEND(090), RECV(098), and
CMND(490) cannot be executed at the same communications port.
Input A remains ON from start to completion of commu-
nications instruction.
Creates operand and control data in a given
area.
Executes communications instructions.
Creates reset input. (Turns reset B ON
after execution of communications in-
struction.)
Send Error Flag display
(Retry can be executed.)
Exclusive control so execution is not simultaneous.
Use exclusive control so that no other communica-
tions instructions are started before execution of the
above communications instruction is complete.
Address
Word
Bits
A202
Bit 7: Port 7
Bit 6: Port 6
Bit 5: Port 5
Bit 4: Port 4
Bit 3: Port 3
Bit 2: Port 2
Bit 1: Port 1
Bit 0: Port 0
A219
Bit 7: Port 7
Bit 6: Port 6
Bit 5: Port 5
Bit 4: Port 4
Bit 3: Port 3
Bit 2: Port 2
Bit 1: Port 1
Bit 0: Port 0
Section 7-2
Contents
OFF: Execution enabled
(being executed)
ON: Execution disabled
(not being executed)
OFF: Normal completion
ON: Abnormal completion

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cj1w-fln22

Table of Contents