Unit Status (Fl-Net Unit To Cpu Unit) - Omron CS1W-FLN22 Operation Manual

100base-tx, sysmac cs / cj series, fl-net units
Table of Contents

Advertisement

Allocated Words in the CIO Area

4-3-10 Unit Status (FL-net Unit to CPU Unit)

15
14
n+6
Bits
Name
0
FA Link Running
1
Readable Transmission
Message
2 to 7
(Not used.)
8
FA Link (Common Mem-
ory) Area Allocation
Error
9
Data Link (PLC) Area
Allocation Error
10
Token Monitoring Time-
out Error
11
LAN Controller Error
13
12
11
10
9
8
7
ON
OFF
ON
OFF
---
ON
OFF
ON
OFF
ON
OFF
ON
OFF
6
5
4
3
2
1
FA Link (Common Memory) Area Allocation Error
Data Link (PLC) Area Allocation Error
Token Monitoring Timeout Error
IP Address Setting Error
Transceiver Error
EEPROM Error
Status
Running
ON when participating in FA link.
Stopped
OFF when not participating in the FA link or
when node numbers have been duplicated.
Yes
ON when transmission of a transparent mes-
sage is completed normally.
No
OFF when a transparent message is read and
disappears from the communications buffer.
---
Error
ON when an error occurs in FA Link (Common
Memory) Area allocations.
The Common Memory allocations for the local
node setup area are incorrect. Correct the set-
tings from the CX-FLnet or FL-net Unit Support
Software.
Normal
OFF when FA Link (Common Memory) Area
allocations are normal.
Error
ON when an error occurs in Data Link (PLC)
Area allocations.
The PLC Area allocations for the local node
setup area and other node setup area are
incorrect. Correct the settings from the CX-
FLnet or FL-net Unit Support Software.
Normal
OFF Data Link (PLC) Area allocations are nor-
mal.
Error
ON when a token monitoring timeout occurs
while the local node is holding the token.
A processing delay has occurred due to high
system load. Correct the system configuration
or extend the token monitoring timeout time
(token watchdog timer) using the CX-FLnet or
FL-net Unit Support Software.
Normal
OFF when a token monitoring timeout does not
occur while the local node is holding the token.
Error
ON when communications are not possible due
to an error.
Normal
OFF when communications are normal.
Section 4-3
0
FA Link Running
Readable Transmission Message
Unit operation
55

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cj1w-fln22

Table of Contents