Wiring Multiple Detectors - Honeywell GX-Series Installation And Setup Manual

Gx series;
Table of Contents

Advertisement

When this wiring mode is employed, only one detector which can report fault conditions should be connected
to the zone. A maximum of two detectors or contacts of any type should be connected to a zone when this
mode is selected. It is recommended that zone cable lengths are kept below 328 feet (100 m) in this
configuration.
NOTE: The recommended maximum cable run from a zone to a detector is 1640 feet (500 m) in all other
configurations.
Option 02 - 1k
Tamper S/C
0 - 800 0 – 1800
Low Res
800 – 900
Normal
900 – 1200
High Res
1200 – 1300
Fault
-
Masked
1300 – 12000
Open
12000 – infinity
Option 10 - 1k Fault End-Of-Line
The wiring in Figure 2-14 should be used if the mode is end-of-line. Fault and mask indications can only be
signaled if the detector has separate fault and mask indications.
Zone
When this wiring mode is employed, only one detector which can report fault conditions should be connected
to the zone. A maximum of two detectors or contacts of any type should be connected to a zone when this
mode is selected. It is recommended that zone cable lengths are kept below 100m in this configuration.
NOTE: The recommended maximum cable run from a zone to a detector is 1640 feet (500 m) in all other
configurations.

Wiring Multiple Detectors

Multiple detectors can be wired into a single zone when using preset 1 as shown in Figure 2-15. The
maximum number of detectors that can be connected to a single zone is ten.
N/C
Zone
Option 04 – 2.2k
0 – 3700
1800 – 2000
2000 – 2500
2500 – 2700
-
2700 – 12000
12000 – infinity
Table 2-7. End of Line Zone Resistance and Conditions
Tamper N/C
Alarm N/C
Figure 2-14. Option 10 - End of Line Zone/Detector wiring
Alarm
Alarm
N/C
N/C
1k
1k
1%
1%
Figure 2-15. Zone to Multiple Detector Wiring
GX-Series Control Panel Installation and Setup Guide
Option 06 – 4.7k
Option 08 – 5.6k
0 – 1400
3700 – 4200
4200 – 5500
5500 – 6500
-
6500 – 19000
9800 – 19000
19000 – infinity
19000 – infinity
3k
Fault N/C
328 ft (100 m)
Alarm
N/C
1k
1%
1640 ft (500 m)
2-13
Option 10 -1k Fault
0 - 800
1400 – 2800
800 - 900
2800 – 8400
900 - 1200
8400 – 9800
1200 - 1300
-
1300 - 4500
4500 - 19000
19000 – infinity
12k
Anti-mask N/C
1k
GX-014-V2
(10 max)
Alarm
N/C TAMP
N/C
1k
1%
1%
GX-015-V1
1k