Intelligent Sensing Applications
Detector Type
Ion
SMOKE (ION)
(See notes * , ** , and
FlashScan View Laser
**
(See Note
)
Acclimate
Multi-Sensor
Heat (Adjustable Threshold)
Beam Detector
††
(See Note
~
Signifies the factory default setting.
* Detectors are suitable for open area protection within the listed air velocity range. Typically, this range is 0 - 4,000 ft/min for
photoelectric detectors and 0 - 1,200 ft/min for ionization detectors. Be sure to confirm this range before installing the
detector by referring to the manufacturer's installation instructions.
Use only alarm sensitivity setting of AL=1, AL=2 or AL=3 for ION detectors installed in Canada.
1% max. on CLIP. Larger figures may display.
** The use of alarm sensitivities below 0.50% obscuration per foot requires a 90 day test to ensure that the environment for the detectors
is suitable for the higher sensitivity setting. (Refer to "To Test Detectors Set Below 0.50% Obscuration per Foot" on page 114.)
†† Refer to the beam detector manual to determine the alarm settings: they are a function of the distance between the detector
and its reflector. There is no Prealarm for beam detectors in CLIP mode.
D.4.2 To Test Detectors Set Below 0.50% Obscuration per Foot
Using alarm sensitivities below 0.50% obscuration per foot requires a 90-day test to ensure that the
detector environment is suitable for the higher sensitivity setting. To meet Notifier and
Underwriters Laboratory requirements, test each detector planned to operate below 0.50%/ft
obscuration as follows:
114
Alarm (FlashScan)
AL:1=0.50 %
AL:2=0.75 %
)
AL:3=1.00 %
AL:4=1.25 %
AL:5=1.50 %
AL:6=1.75 %
AL:7=2.00 %
AL:8=2.25 %
AL:9=2.50 %
AL:1=0.02 %
AL:2=0.03 %
AL:3=0.05 %
AL:4=0.10 %
AL:5=0.20 %
AL:6=0.50 %
AL:7=1.00 %
AL:8=1.50 %
AL:9=2.00 %
AL:1=0.50 %
AL:2=1.00 %
AL:3=1.00 to 2.00 %
AL:4=2.00 %
AL:5=2.00 to 3.00%
AL:6=3.00 %
AL:7=3.00 to 4.00 %
AL:8=4.00 %
AL:9=thermal 135
AL:1=43
AL:2=57
AL:3=63
AL:4=68
AL:5=74
AL:6=88
AL:7=88
AL:8=88
AL:9=88
AL:1=25%
)
AL:2=30%
AL:3=40%
AL:4=50%
AL:5=30 - 50%
AL:6=40 - 50%
Table D.2 Detector Sensitivity Settings
~
~
Alarm (CLIP)
AL:1=1.00 %
AL:2=1.00 %
AL:3=1.00 to 2.00 %
AL:4=2.00 %
~
AL:5=2.00 to 4.00%
AL:6=2.00 to 4.00%
AL:7=2.00 to 4.00%
AL:8=4.00 %
o
F
AL:9=4.00%
°
C
°
C
~
°
C
°
C
°
C
°
C
°
C
°
C
°
C
NFS2-3030 Programming Manual — P/N 52545:A 11/29/2005
Detector Sensitivity Settings
Pre-Alarm
PA:1=Auto
PA:2=0.40 %
PA:3=0.50 %
PA:4=0.75 %
PA:5=1.00 %
~
PA:6=1.25 %
PA:7=1.50 %
PA:8=1.75 %
PA:9=2.00 %
PA:1=Auto
PA:2=0.02 %
PA:3=0.05 %
PA:4=0.10 %
PA:5=0.20 %
~
PA:6=0.50 %
PA:7=0.70 %
PA:8=1.00 %
PA:9=1.50 %
PA:1=0.50%
PA:2=1.00 %
PA:3=1.00 %
PA:4=1.00 to 2.00%
~
~
PA:5=1.00 to 2.00 %
PA:6=2.00 %
PA:7=2.00 %
PA:8=2.00 to 3.00 %
PA:9=2.00 to 3.00 %
°
PA:1=40
C
°
PA:2=43
C
~
°
PA:3=57
C
°
PA:4=65
C
°
PA:5=70
C
°
PA:6=75
C
°
PA:7=75
C
°
PA:8=75
C
°
PA:9=75
C
PA:1=50%
PA:2=55%
PA:3=60%
PA:4=65%
PA:5=70%
PA:6=75%
PA:7=80%
PA:8=85%
PA:9=90%