Wiring Multiple Zones; Wiring Keyswitches - Honeywell Galaxy 3-48C Installation Manual

Hide thumbs Also See for Galaxy 3-48C:
Table of Contents

Advertisement

Galaxy 3 Series Installation Manual
Zone
Figure 2-12. Preset 1 - Double balanced Zone/Detector wiring
Zone
NOTE: N/C = Normally Closed
NOTE: The recommended maximum cable run from a zone to a detector is 500 metres.

Wiring Multiple Zones

Multiple detectors can be wired into a single zone as shown in the following Figure. The maximum number of
detectors that can be connected to a single zone is ten.
Zone

Wiring Keyswitches

Latching or spring loaded keyswitches can be used to set and unset the Galaxy panels; option 52 = PRO-
GRAM ZONES has provision to accommodate both types of transition.
If the keyswitch latches, the transition from 1 kΩ to 2 kΩ initiates the setting procedure of an unset system,
the transition from 2 kΩ to 1 kΩ instantly unsets a set system. If the system is already set, then the transition
from 1 kΩ to 2 kΩ has no effect. If the system is unset, the transition from 2 kΩ to 1 kΩ has no effect. This
is programmed as a
Keyswitch in the PROGRAM ZONES option.
If the keyswitch is spring-loaded (returns to its normal position), the transition from 1 kΩ to 2 kΩ initiates the
setting procedure of an unset system and instantly unsets a set system, the transition from 2 kΩ to 1 kΩ - the
return to the normal position - has no effect. This is programmed as a Keyswitch in the PROGRAM
ZONES option.
Alarm
1k
1%
Alarm
Figure 2-13. Preset 1 - End of Line Zone/Detector wiring
Alarm
Alarm
N/C
N/C
1k
1k
1%
1%
Figure 2-14. Zone to Multiple Detector Wiring
Tamper
N/C
N/C
500 m
Tamper
N/C
N/C
500 m
Alarm
N/C
N/C
1k
1%
500 m
2-15
Zone Wiring
Anti-mask
N/C
12k
1k
1%
1%
Anti-mask
N/C
12k
1k 1%
1%
(10 max)
Alarm
N/C TAMP
N/C
1k
1k
1%
1%