Exiting from Engineer (Installer) Mode
To exit from Engineer mode and return to the normal banner enter, carry out the following operation:
1. Return to the Engineer banner.
2. Enter the Engineer code.
3. Press the esc key.
The GX-Series carries out the following checks:
1. That there are no module or zone tampers. If there are any module or zone tampers the exit procedure is
aborted.
2. That it is communicating with all of the attached modules. If any modules are reported as missing from
the system, the GX-Series prompts the Engineer to remove each of the missing modules by pressing the
* key. If the Engineer does not remove the missing modules, the exit procedure is aborted.
3. That all of the access doors are closed. If any of the access doors are open, then the exit procedure is
halted until all of the doors are closed.
4. That there are no power failures on the GX-Series system, such as AC fail or battery fail.
Aborting the Exit Engineer Mode Procedure
If the esc key is pressed at any point while Engineer mode is being exited, before the normal banner is
displayed, the exit procedure is aborted and the system remains in Engineering mode.
Multi User Access
The GX-Series allows multi-user access. A maximum of 16 users can simultaneously carry out tasks on the
system.
GX-Series Control Panel Installation and Setup Guide
6-3