Power-limited Wiring Requirements

2.5 Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All
power-limited circuit wiring must remain at least 0.25" (6.35 mm) away from any nonpower-
limited circuit wiring. Furthermore, all power-limited and nonpower-limited circuit wiring must
enter and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram
for the Flex 404 is illustrated below.
Power-limited Circuits
+
Nonreset
J9
J7
AC Power
Figure 2.9 Typical UL Power-limited Wiring Requirements
Flex 402 & Flex 404 Instruction Manual — P/N 52194:D4 3/27/2015
-
+
-
A+
A-
A+
A-
A+
A-
A+
Resettable
CLASS A CLASS A
CLASS A CLASS A
NAC 1
NAC 2
ZONE 1
ZONE 2
CAC-4
FIRE ALARM
SUPERVISORY
FIRE ALARM
SUPERVISORY
FIRE ALARM
SUPERVISORY
FIRE ALARM
SUPERVISORY
NAC
ZONE
NAC
AC
DISABLE
DISABLE
FAULT
POWER
ALARM
ACK
SILENCE
ENABLE/DISABLE
1
2
TB8
HOT NEUT EARTH
Nonpower-limited Circuits
C
NC NO
A-
A+
A-
A+
A-
ALARM
4XLB
CLASS A CLASS A
ZONE 3
ZONE 4
ZONE 1
TROUBLE
MAINTENANCE
ZONE 2
TROUBLE
MAINTENANCE
ZONE 3
TROUBLE
MAINTENANCE
ZONE 4
TROUBLE
MAINTENANCE
ALARM
POWER
WALK
SYSTEM
TROUBLE
TEST
SILENCE
TROUBLE
WALK
RESET
TEST
ZONE
3
4
JP1
JP2
EARTH BATT CHG
J8
BATTERY
SW1
SW2 SW3
Installation
C
NC NO
SUPV
Power-limited
Circuits
4XLMF
4XTMF
Nonpower-limited
Circuit
23

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fci gamewell flex 402

Table of Contents