19 Fire {Not for UL installations}
The Fire function is continuously operational. When activated, a FIRE zone overrides the Bell Delay
parameter and activates an instant alarm (Bell, Strobe and Fire). The keypad buzzer and control panel
horn output, if installed, emit an interrupted tone (one second on, 0.5 seconds OFF), easily distinguishable
from all other alarm conditions. Any valid code entry cancels the Fire activation.
20 Tamper
The Tamper function is continuously operational. When a Tamper zone is activated (1kΩ to 2kΩ), a tamper
alarm is generated; this requires to be reset by a code authorized for Tamper Reset - refer to option 51.7 =
PARAMETERS.Tamper Reset. If a tamper condition (open or short circuit) occurs, a tamper alarm is also
generated.
21 Bell Tamper
This function is identical to the operation of the Tamper function but is dedicated to bells, sirens and other
modules or output devices requiring tamper protection.
22 Beam Pair
This function is only operational when two consecutively addressed zones programmed as Beam Pair are
open in the set condition; the activation is identical to the Intruder function. The system cannot set (arm) if
a single Beam Pair is open.
NOTE: Beam Pair zones must be consecutively addressed; the first Beam Pair zone must have an even number
address, the second Beam Pair must have the next address (an odd number). For example, valid Beam Pair
addresses are 1036 & 1037, 2018 & 2031 - in this case, RIO 202 has not been connected, therefore zone 2031 is
the next address to 2018.
23 Battery Low
This function is used to monitor the voltage output of a standby battery connected to a power supply. The
activation (+) and de-activation (–) of Battery Low zones is recorded in the event log.
24 Line Fail
The Line Fail function is used to monitor the communication line that a remote signaling device is
connected to for communications failure.
When the system is in the unset (disarmed) state, the first activation of a Line Fail zone causes a local
alarm and the message COMMS FAILURE is displayed, subsequent Line Fail activations do not sound
the local alarm; the only indication is the keypad display.
When the system is set (armed), activation of the Line Fail zone overrides the Bell Delay parameter; on
unsetting (disarming) the system a local alarm is generated and the keypad gives an indication that Line
Fail zone has activated. If an alarm condition occurs while the Line Fail is active, an instant full alarm is
generated.
If the Line Fail zone is active at the point of setting (arming), a warning message is displayed; the user can
choose to continue or abort the setting (arming) procedure. It is also possible to prevent the system setting
(arming) if the Line Fail is active by enabling the Stop Set parameter (option 51.18).
25 AC Fail
This function is used to monitor a remote power supply. In the event of a power failure the AC Fail zone is
activated; the activation (+) and de-activation (–) of the zone is recorded in the event log.
26 Log
This zone type has no operational function; it is designed to record the activation of a zone in both the set
(armed) and unset (disarmed) state. The activation (+) and de-activation (–) of Log zones is recorded in the
event log.
27 Remote Access
This function is used to disable remote servicing of the GX-Series panel. When the Remote Access zone is
active the Remote Servicing software is prevented from gaining access to the GX-Series panel.
6-61