Programming Example:
Zone 1014 = An on/off keyswitch programmed as Exitguard.
Zone 1015 = A door contact programmed as Security.
Output type Link A = An output wired to a local horn and programmed as Link A.
NOTE: Exit Guard zones do not omit zones open when the exit guard zone is activated, even if they are
subsequently closed.
Operation: The Security door contact (1015) can be omitted at any time by operating the Exitguard
keyswitch (1014). If the door (1015) is opened without first being omitted, then the Link A horn activates
and needs to be reset by operating the keyswitch (1014).
36 Mask
The Mask function is designed to be used with detectors capable of reporting that their field of view has
been blocked or masked. The Mask function is identical to the Security function, with the exception that
the Mask output is activated instead of Security.
NOTE: This zone type is independent from the mask zone state which can be detected for zones supporting the
masked feature.
37 Urgent
The Urgent function is continuously operational; it is identical to the Intruder function, with the exception
that it activates a full alarm condition (including the Intruder outputs) in any set (armed) or unset
(disarmed) condition.
38 PA Unset
This PA Unset function is identical to the PA Silent function, with the exception that it is only operational
when the system is unset (disarmed); the function is inactive when the group is set (armed).
39 Keyswitch Reset
The Keyswitch Reset function allows alarms to be cancelled and the system to rearm without unsetting
(disarming) the GX-Series. The type of reset authorization is determined by the Keyswitch Level (option
51.14). The type required to reset Intruder, PA and Tamper alarms is determined by the System Reset,
Tamper Reset and PA Reset parameters (option 51.06, 51.07 and 51.22) respectively.
This function is designed to permit a remote signal, for example REDCare's Return Path Signaling feature,
to reset the system following an alarm condition.
40 Bell Fail
This zone type is intended for bells which have diagnostic capabilities and failure outputs. If activated, this
zone causes a fault condition.
41 Intr Low
This zone type assigns a low priority to a zone in the event of an intruder alarm. The event is logged as low
priority in the event log.
42 Intr High
This zone type assigns a high priority to a zone in the event of an intruder alarm. The event is logged as high
priority in the event log.
43 PSU Fault
This zone type triggers a general fault output and logs a PSU fault in the event log. The fault is signaled to
the ARC as YP when using SIA format and 314 when using CID format.
GX-Series Control Panel Installation and Setup Guide
Link
Source
1
Zone = 1014
2
Zone = 1015
3
Zone = 1014
Table 6-17. Exit Guard Zones
6-63
Destination
Zone = 1015
Output = Link A
Output = Link A