GX-Series Control Panel Installation and Setup Guide
47 U/S Early (Latch)
The Unset Early output is activated if the system has been unset (disarmed) before the programmed
Monitor time – refer to option 65.3.1=TIMERS.Autoset.Status.
48 Prewarn (Reflex)
The Prewarn output is active during the programmed prewarning period of the autoset function. The mode
is Reflex. The Prewarn emits a constant tone if the autosetting of the system can be extended. If an
extension is not possible, the Prewarn output pulses.
49 Autoset (Reflex)
The Autoset output is activated when the system has been set (armed) by the autoset function – refer to
option 65.3=TIMERS.Autoset. The default Output Mode attribute is programmed as Reflex, therefore the
output remains active until the system unset (disarms).
NOTE: The Set is also activated when the system autosets.
50 DR. Masked
The DR. (detector) Masked output is activated when zones, programmed for zone activity checks, are not
activated in the unset (disarmed) state within the time period or set/unset (armed/disarmed) cycles
programmed in Parameter 51.61. The zones are programmed for activity in menu 52.8.
51 – 65 Link A – O (Reflex)
Link output types have no inherent function: they are designed for use with option 54 = LINKS to provide
the engineer with a means of activating a specific output address.
Link outputs can be activated by any of the link option sources. The operation of the Link output is
dependent on the Output Mode and Groups assigned to the output. The Groups assigned to the Link
must have at least one group common to the link output, if that output is to be activated. This feature can be
used to multiply the number of different link outputs available on the system.
NOTE: When a zone function is the source of a Link output type, then a point to point link is available and is as
effective as direct wiring.
66 NOT USED
67 NOT USED
68 Bell Fail
The Bell Fail output activates whenever a zone causes a fault condition.
69 Low Volts
The Low Volts output activates when the voltage of the AUX outputs drops below 10V.
70 Lockout (Reflex)
The Lockout output is active between the ON and OFF times assigned to the Lockout Status (option
65.3.6=TIMERS.Autoset.Lockout Status). The Lockout output mode is Reflex, therefore it remains
active until the lockout switches OFF.
71 Vibration Test (Pulse)
The Vibration Test function is used to test zones programmed as Vibration. This output is used in
conjunction with Precheck (menu option 66 – Pre-Check: - Mode: 4 – Forced Check). The Vibration Test
output sends a five second positive removed pulse to the vault sensors. Any sensor not activated by the test
is reported by the pre-check function and prevents the system from setting (arming).
72 – 75 ATM-1, ATM-2, ATM-3, ATM-4 (Reflex)
The relevant ATM output is activated when the respective ATM zone type is omitted (bypassed). This
output is a Reflex output and follows the omit status of the ATM zone types.
76 Fault (Latch)
This output will activate any time there is a fault condition present on the panel and will clear when all the
fault conditions have cleared.
6-77