GX-Series Control Panel Installation and Setup Guide

SECTION 1: QUICK SETUP

To quickly set arm up a GX-Series control panel for programming follow these simple steps:
1. Connect a 1k • resistor across each of the zones on the panel and any RIO's (if connected).
2. Ensure that the tamper return loop — the terminals marked as AUX TAMP/GND on the PCB — is a
complete loop.
3. Connect a keypad to the AB LINE terminals on the control panel.
4. Connect a 680 • End Of Line (EOL) resistor across the A and B terminals of the keypad.
5. Ensure that the keypad is installed on the wall (see Keypad Installation Procedure, Section 4).
6. Connect the battery.
7. Connect the AC wiring to the control panel.
8. Switch on the AC power and remove the protective cover from the PCB battery.
9. The following sequence of events occur:
the keypad buzzer and control panel horn (if installed) activate for 10 - 20 seconds,
flashing *************** is displayed on the keypad,
the sounders stop and the keypad displays become blank,
the green power LED lights and the following displays on the keypad
the default banner is then displayed on the keypad.
GX
01:01
where: XXX is the panel type
Y.YY is the panel software revision
10. The system is now ready to be programmed. Refer to Section 6 System Operation for programming
details.
11. Default User code is 12345
Default Engineer (Installer) code is 112233