Default Codes
The GX-Series system provides four default codes: Manager, Installer (Engineer), Remote and Authorization
User. Refer to the following table:
No. of
Default
Codes
Panel
GX-48
100
GX-520
1000
* The authorization code is a secondary system manager code but is not programmed by default.
Engineer Code
Engineer access is enabled via menu 48.1. This menu is only available to type 3.6 users.
The engineer code can only modify the engineer PIN.
The engineer code cannot assign, modify or delete the manager or user codes;
On accessing engineering mode, any group that is set (armed) becomes inaccessible to the engineer.
The set (armed) groups cannot be assigned to zones, outputs and any other functions permitting
group allocation;
While engineer mode is accessed, all tampers are disabled, however, all constantly alert zone types
— PA zone types, 24 Hour, Security, Fire — remain active.
The engineer banner is shown on all keypads while engineer mode is being accessed; the message
ENGINEER MODE is displayed;
Entry to the engineer mode must be authorized by a valid type 3.6 user (Manager; refer to option 48 =
ACCESS AUTHORIZATION). The engineer code must then be entered within five minutes of the option
being enabled. A single entry of the engineer code directly accesses engineer mode, without activating an
engineer tamper alarm; ENGINEER MODE is displayed on the keypad. If the engineer code is not entered
within the five minute period, the code is invalid and an Insufficient Access Rights message is displayed
on the keypad. Once the engineer mode has been accessed, there is no time limit on the period that the
engineer can remain in the mode.
NOTE: Dual entry of the engineer code in a system requiring user authorization does not give access to engineer
mode.
ATM User Codes
{Not for UL installations}
ATM (Automatic Teller Machine) user codes work in conjunction with ATM zone types (refer to Menu Option
52.48-51=Program Zones ATM1-4). ATM user codes cannot be used as normal user codes for setting
(arming) / unsetting (disarming), etc., 94 to 96 user codes for each GX-48 and 986 to 995 user codes for each
GX-520 that are dedicated as ATM users.
Exiting from Engineer Mode
1. Return to the engineer banner.
2. Enter the engineer code.
3. Press the esc key.
The GX-Series begins the exit engineer mode procedure by checking the integrity and security of the system:
CHECKING FOR TAMPERS — the panel calculates that the standby battery connected to it is
capable of operating the system for the required period (as entered in the Standby Battery
parameter — refer to option 51.37). The system then verifies that there are no tamper conditions
present on the panel, the modules or the zones.
SYSTEM MODULES — if there are no tamper conditions the GX-Series checks the number of
modules connected to the system:
Manager
Installer (Engineer)
Default
PIN
User No.
12345
98
112233
12345
998
112233
Table 6-4. Default Codes
GX-Series Control Panel Installation and Setup Guide
Default
PIN
User No.
PIN
99
542310
999
543210
6-21
Remote
Authorization*
Default
User No.
PIN
100
-
1000
-
User No.
97