1: Intelligent Addressable Detectors; 2: Intelligent Addressable Modules; 3: Addressable Device Accessories; End-Of-Line Resistor Assembly - Honeywell Fire-Lite Alarms ES-1000X Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Product Description
IPOTS-COM
The IP/POTS Communicator card, standard on the ES-1000X and ES-1000XC, transmits system status (alarms, troubles, AC loss, etc.) to a
Central Station via the public switched telephone network. It also allows remote programming or interrogation of the control panel using the
FS-Tools Upload/Download utility and a hard-wired ethernet IP connection. Any personal computer with Windows
bit, and FS-Tools software may serve as a Service Terminal. This allows download of the entire program or upload of the entire program, his-
tory file, walktest data, current status and system voltages. Refer to Section 6 on page 119 for more information.
The IPOTS-COM digital communicator provides the following functions:
Line Seizure: takes control of the phone lines disconnecting any premises phones
Off/On Hook: performs on and off-hook status to the phone lines
Listen for dial tone: 440 Hz tone typical in most networks
Dialing the Central Station(s) number: default is Touch-Tone
For tone burst or touchtone type formats: discern proper Ack and Kissoff tone(s). The frequency and time duration of the tone(s) varies
with the transmission format. The control panel will adjust accordingly.
Communicate in the following formats:
Ademco Contact ID
SIA DCS 8
SIA DCS 20
Cabinet
The ES-1000X backbox provides space for two batteries (up to 26 Amp Hour). Ample knockouts are provided for system wiring. A dress
panel comes standard with every cabinet.
Dress Panel
A dress panel comes standard with the ES-1000X. The dress panel restricts access to the system wiring while allowing access to the keypad.
Batteries
Batteries larger than 55 Amp Hour require an external charger such as the CHG-75 or
CHG-120F and a UL listed battery box such as the BB-26 or BB-55F. Batteries must be
ordered separately.
1.4.1 Intelligent Addressable Detectors
Intelligent, addressable detectors provide information to the control panel on an SLC Signaling Line Circuit (refer to the SLC Wiring Manual
for detailed information on device installation, wiring and operation). This allows the control panel to continually process the information to
determine the status (alarm, trouble, maintenance or normal) of each detector. Each detector responds to an SLC address that is set in the
detector head using built-in rotary decimal switches. The maximum address cannot exceed address 159. Note that a blinking LED on an
intelligent detector indicates communication between the detector and the control panel.
These devices (350 Series or newer) can operate in CLIP mode (Classic Loop Interface Protocol) or LiteSpeed mode to provide a quicker
response. They are also compatible with older 300 Series devices. If a mix of old and new series devices are installed on the same loop, the
FACP must be programmed to operate in CLIP mode. Refer to the SLC Wiring Manual for a list of compatible addressable detectors.
1.4.2 Intelligent Addressable Modules
Control Modules and Monitor Modules provide an interface between the control panel and conventional notification and initiating devices.
Each module can be set to respond to an address with built-in rotary switches. The maximum address cannot exceed address 159. Note that a
blinking LED on an addressable module indicates communication between the module and the control panel.
These devices (i.e., MMF-300, MDF-300, MMF-301, MMF-302, CMF-300, CRF-300) can operate in CLIP mode (Classic Loop Interface
Protocol) or LiteSpeed mode to provide a quicker response. They are also compatible with older 300 series devices. If a mix of old and new
series devices are installed on the same loop, the FACP must be programmed to operate in CLIP mode. Refer to the SLC Wiring Manual for
a list of compatible addressable modules. Refer to the Device Compatibility Document for a list of approved conventional notification and
initiating devices.
1.4.3 Addressable Device Accessories

End-of-Line Resistor Assembly

The End-of-Line resistors are included with each module. Refer to the specific module documentation for specific information.

Power Supervision Relay

The UL listed End-of-Line power supervision relay is used to supervise the power to 4-wire smoke detectors and notification appliances.
16
®
, programmable to rotary
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
Components
®
7 or greater, 32 or 64
Battery Cable P/N 75287

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fire-lite alarms es-1000xcFire-lite alarms es-1000xi

Table of Contents