56.1.14 Alarm Monitoring {Not evaluated by UL}
This option is used to allow events to be dialed to a PC with Alarm Monitoring software loaded.
The Alarm Monitoring option transmits alarm events information only when all of the alarms have been
sent to the ARC (or all seven of the communication attempts have been unsuccessfully made). If a new alarm
event occurs while the system is transmitting in the Alarm Monitoring mode, the transmission is
terminated and the alarms are sent to the ARC using the primary format selected.
The menu structure and programming of the Alarm Monitoring options are identical to the SIA format.
Refer to option 2 = SIA for programming details.
56.1.15 Backup Module
This option allows another module to become the primary communication module if a line fail is detected on
the on-board telecom. There are 3 options:
1 = Off
2 = NOT USED
3 = NOT USED
4 = NOT USED
5 = Ethernet
6 = Int RS232 1.
56.1.16 Force V.21
Option not available
56.1.17 SMS {Not for UL installations}
The SMS option is available on GX-Series panels with V4.00 and above software and Telecom modules with
V5.xx and above software. This option generates and transmits SMS text messages, for events generated by
the GX-Series panel.
1=Mobile No.
This is a 22 digit telephone number and is the mobile phone number of the recipient of the message.
2=Centre No.
This is a 22 digit telephone number and is the phone number of the SMS centre. The default is different
for each operator.
3=Format
The options for this menu are:
1=TAP
For mobile phones
2=UCP (SMS)
For mobile phones
3=UCP (Minicall)
For alpha pagers
4=UCP (Numeric)
For numeric pagers
4=Site ID
This is a 16 character alphanumeric string and is used to identify the panel/site sending the
message. If the format is UCP (Numeric), then the site ID is numeric only, and only the first four
characters are sent out.
5=Password
This is a 16 character string and is an optional field required by some paging centers.
GX-Series Control Panel Installation and Setup Guide