GX-Series Control Panel Installation and Setup Guide
31 = Delay Alarm
This parameter determines the delay between the activation of an Intruder Delay zone and the alarm
sounding or a Log Delay zone being recorded as opening in the event log. The Delay Alarm is
programmable within the range 0–3000 seconds; the default is 60.
If a second Intruder Delay zone opens followed by the first zone closing, the Delay Alarm time continues
to count from the activation of the first zone. The Delay Alarm timer is reset only when all delay type zones
return to the closed state.
This parameter can be assigned a different value for each group.
32 = Show Alarms
If the Show Alarms parameter is enabled, the first alarm activation is immediately displayed on all the
keypads when an alarm condition occurs. Normally alarm messages are not displayed until the alarm is
cancelled by entry of a valid code. Parameter 51.63, Banner Alerts must be enabled to view alarms on the
keypad banner.
0 = disabled (default)
1 = enabled
NOTE: This parameter will only function when at least one group is unset (disarmed).
33 = Secure Code
Once this parameter has been selected, the engineer code is randomly changed each day at 08:00 hours. The
service engineer must be informed of the "code of the day" by head office. The random code that is generated
is dependent on the local engineer code; therefore each area, company, branch or even system can have a
unique secure code.
Either the engineer or remote user code can select the Secure Code parameter. On selecting this parameter
the secure code equivalent to the current engineer code must be entered to confirm the selection. Only the
remote user code (or a cold start - erasing all programming details) can cancel it.
Select 1 to enable Secure Code, or 0 to disable the parameter; the default is 0 (disabled).
34 = Comfort Time
The Comfort Time parameter permits a period of time to be allocated when the values assigned to the
entry and abort time parameters and the number of wrong code attempts are doubled; the programmable
range is 0–14 days; the default is 0. This allows new or unfamiliar users to become accustomed to the system
without causing false alarm activations. At the end of the Comfort Time the system returns all the affected
parameters to the programmed values.
35 = Fail to Set
This parameter determines the period of time that a zone must remain open, following the start of the
setting (arming) procedure, before the Fail Set outputs activate. The programmable range is 0–999 seconds;
the default is 360.
NOTES: 1. The Fail to Set countdown time begins as soon as the setting (arming) procedure is started.
2. The Fail to Set time should be at a minimum 5 seconds longer than the Exit Time (option 51.04),
to allow for the setting (arming) period to expire.
This parameter can be assigned a different value for each group.
36 = Battery Size
Enter the size of the standby battery on the control Panel PSU. The programmable range is 0–99Ah; the
default is 0.
37 = Standby Time
Enter the value (in hours) that the system is required to run on standby battery if there is a mains fail. The
programmable range is 0–99 hours; the default is 0.