5.8. Configuring non-cache parameters

Scenario
the device goes off
the network.)
Disabling the
reporting of the Block
Offnet Diagnostic
Alarm for an
individual FF function
block when the
device is online.
Disabling the
reporting of the Block
Offnet Diagnostic
Alarm for an
individual FF function
block when the
device is off the
network.
5.8
Configuring non-cache parameters
To configure non-cache parameters, perform the following steps.
WARNING
The non-cache capability bypasses the normal data-acquisition optimizations
which are implemented by FIM. Configuring or monitoring the non-cache
parameters can lead to performance degradation or visible anomalies
Therefore, you must configure non-cache parameters under special
circumstances recommended by Honeywell, Inc. or device vendors.
Step
1
On the Project mode, right-click the device instance to select Module
Properties.
The configuration form appears.
238
Experion PKS Series A Fieldbus Interface Module User's Guide
Behavior of Block Offnet Alarm
A change event is logged in the
Event Summary indicating
OFFNETALM_ENABLED is set to
OFF.
The previously reported Block
Offnet Alarm for that function
block changes from "Active" to
"Disabled" in the Alarm Summary.
A change event is logged in the
Event Summary indicating
OFFNETALM_ENABLED is set to
OFF.
Honeywell
Behavior of Device Offnet System
Alarm
There is no change to the Device
Offnet System Alarm.
Action
R400
July 2010