5. Configuration
5.4. Configuring Fieldbus Components In a Control Strategy
Making fieldbus block template and assigning function block to device
The following procedure outlines the steps for making user template for a function block
in the Fieldbus Library in Project, adding the block to an instantiated Control Module in
Project, and assigning the block to a fieldbus device. The following procedure makes and
assigns a fieldbus analog input block template for example purposes only. You can easily
adapt this procedure to apply to another Fieldbus Library block. The illustrations in this
procedure are for example purposes only.
Step
1
In Project mode, click Library tab, click +
sign for FIELDBUS, and click AI block
icon.
2
Click Templates->Make Template.
164
Experion PKS Series A Fieldbus Interface Module User's Guide
Action
Honeywell
Result
Selects fieldbus Analog Input (AI) block
in the FIELDBUS Library.
Calls up AI Block configuration form.
R400