10. Appendix A
10.2. Standard Function Blocks
SEL_1
SEL_2
SEL_3
BKCAL_IN
Selection
SEL_1
SEL_TYPE
SEL_2
SEL_3
Mode

Figure 42 Functional schematic for Control Selector function block.

Description
Function Notes
394
Experion PKS Series A Fieldbus Interface Module User's Guide
OUT
BKCAL_SEL_1
CS
BKCAL_SEL_2
BKCAL_SEL_3
BKCAL_IN
OUT_LO_LIM
The Control Selector function block accepts input from up
to three control signals and selects one for output based on
the SEL_TYPE setting of High, Middle, or Low. A functional
schematic of the block is shown in the previous illustration
for reference.
All inputs must have the same scaling as OUT, since
any one can be selected for OUT.
Supports Out of Service (OOS), Initialization Manual
(IMan) Local Override (LO), Manual (Man), and
Automatic (Auto) modes.
If an input has a sub-status of Do Not Select, it will not
be selected.
Three separate back calculation outputs
(BKCAL_SEL_1, 2, 3) are available - one for each
Honeywell
Output
OUT
OUT_HI_LIM
Back Calc
BKCAL_SEL_1
BKCAL_SEL_2
BKCAL_SEL_3
R400
July 2010