11. Appendix B
11.1. Standard Function Block Parameters
ROUT_OUT
Classification
Description
FF Data Type
Range
Usage
Length
Valid Views
Storage
Remarks
RS_STATE
Classification
Description
FF Data Type
Range
474
Experion PKS Series A Fieldbus Interface Module User's Guide
Record
Represents block output and status. It serves as input to a
host for back calculation in ROut mode that allows action to
be taken under limited conditions or mode change
DS-65
C/Remote-Output Out
5
VIEW_3
Dynamic
Read Only
The data type consists of the value and status of floating
point parameters that are Inputs or Outputs. It uses the
following two elements.
1 Status
2 Value
Simple Variable
Defines the state of the function block application state
machine.
Unsigned 8
1: Start/Restart
2: Initialization
3: On-Line Linking
4: On-Line
5: Standby
Honeywell
R400
July 2010