11. Appendix B
11.1. Standard Function Block Parameters

SHED_OPT

Classification
Description
FF Data Type
Range
Usage
Length
Valid Views
Storage
Remarks

SHED_RCAS

Classification
478
Experion PKS Series A Fieldbus Interface Module User's Guide
Simple Variable
Defines action to be taken on remote control device timeout.
Unsigned 8
1: Normal Shed, normal return -See Note 1 in Remarks
2: Normal Shed, no return - See Note 2 in Remarks
3: Shed to Auto, normal return
4: Shed to Auto, no return - See Note 3 in Remarks
5: Shed to Manual, normal return
6: Shed to Manual, no return - See Note 4 in Remarks
7: Shed to Retained target, normal return (Not used in
Experion)
8: Shed to Retained target, no return ((Not used in
Experion)
C/Shed Option
1
VIEW_4
Static
Note 1: Actual mode changes to the next lowest priority
non-remote mode permitted but returns to the target remote
mode, when the remote computer completes the
initialization handshake.
Note 2: Target mode changes to the next lowest priority
non-remote mode permitted. The target remote mode is
lost, so there is no return to it.
Note 3: Target mode changes to Auto on detection of a
shed condition.
Note 4: Target mode changes to Man on detection of a
shed condition.
Simple Variable
Honeywell
R400
July 2010