Step
TIP
If errors are detected, they will be listed and you will be prompted to select whether or
not you want to continue the load with errors. It is a good idea to note the errors and
abort the load (close), so you can go back and correct the errors before completing the
load. The following illustration is for example purposes only and the errors listed are
not typical.
If the load generates errors identifying subschedule problems, you must
reconfigure the Link Master capable device to become a Basic one through
Control Builder, and restart the device to initiate the change. Otherwise, if the
FIM fails, the potential for a "no schedule" condition exists. Since the
schedule is cleared from the Link Master capable device upon the detection
of subschedule load errors, it cannot function as the backup LAS without a
schedule.
Please see the
Checking/changing fieldbus device functional class section for details on
reconfiguring a device as a Basic type.
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
July 2010
Action
Honeywell
5. Configuration
5.5. Loading Components Online
Result
223