5. Configuration
5.5. Loading Components Online
If the Device
ID is . . .
Not specified.

Loading a CIOM-A FIM and its Links

The following procedure outlines the typical steps used to "load" a CIOM-A FIM
through the Project tab in Control Builder. It assumes that the FIM and its associated
RTP are installed and capable of communicating with the system.
TIP
If present, it is a good idea to load the CPM and its CEE first to verify the
supervisory communications path.
Step
1
Check that the OK LED on the front of
the CIOM-A FIM is flashing and the
numbers 1 and 2 are sequencing in the
left-hand LED on its front panel display.
208
Experion PKS Series A Fieldbus Interface Module User's Guide
And, the Device
State Is . . .
Operational
The device ID (DEV_ID), physical device tag
(PD_TAG), and node address (ADDR) must
match those specified through configuration in
Control Builder. Any mismatch results in an
error.
Initialized
The physical device tag (PD_TAG) must match.
If the desired node address (ADDR) is not in
use, FIM will assign it to the device.
Operational
The physical device tag (PD_TAG) and node
address (ADDR) must match those specified
through Control Builder. Any mismatch results in
an error.
Action
Honeywell
Then, the matching rule is . . .
Result
Confirms that the designated CIOM-A
FIM is operating.
(If ALIV appears in the CIOM-A FIM's
front panel display, you must load the
CIOM-A FIM's personality firmware
before proceeding.)
R400
July 2010