Remarks

FSTATE_TIME

Classification
Description
FF Data Type
Range
Usage
Length
Valid Views
Storage
Remarks

FSTATE_VAL

Classification
Description
FF Data Type
Range
Usage
Length
Valid Views
Storage
Remarks
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
July 2010
11.1. Standard Function Block Parameters
Read Only
Simple Variable
Represents the reaction time in seconds from the detection
of a failure at the output block remote set point to the output
block action, if the condition still exists.
Float
Positive
C/Contained
4
VIEW_4
Static
Simple Variable
Defines the preset analog set point to use when a failure
occurs. Value is ignored, if the IO_OPTS Fault state to
value option is false.
Float
PV_SCALE +/- 10 percent
C/Contained
4
VIEW_4
Static
Honeywell
11. Appendix B