8. Maintenance, Checkout, and Calibration

8.7. Using Fieldbus Device Simulate Function

Step
5
To change the address, key in
desired address. Use 24 for this
example. Press <Enter>.
To clear the address, just highlight
it and press <Delete>. Click the OK
button.
6
Click the Continue button.
7
Wait for change to complete. Click the Ok
button.
8
Confirm that the tag for the
uncommissioned device icon in the
Monitoring tab has changed or has been
cleared (NoTag_248). This completes the
tag and address changes for the
uncommissioned device
8.7
Using Fieldbus Device Simulate Function
Some of the standard fieldbus function blocks support a signal simulation function for
testing purposes only. The following procedure shows the general steps involved in using
the simulate function with an Analog Input block in a Honeywell ST3000 transmitter. All
the illustrations used in the procedure are for example purposes only. You can easily
adapt this procedure to any applicable fieldbus device.
334
Experion PKS Series A Fieldbus Interface Module User's Guide
Action
Only use the simulate function when the system is offline or in a safe
operating mode for testing purposes.
Honeywell
Result
Warning prompt asks for confirmation of
change.
Initiates change and opens progress
tracking dialog box to show status of the
change.
Closes the Link Parameter form.
R400
July 2010