8. Maintenance, Checkout, and Calibration

8.9. Interpreting Component LED Indications

ATTENTION
You can also create the device type template by selecting device type from
the device list. The OverWrite feature reconfigures the configuration forms to
include the "Enable Block Offnet Diagnostic Alarm" check box.
8.9
Interpreting Component LED Indications

CIOM-A FIM LED indications

As shown in the illustration below, the CIOM-A FIM has one four-character display and
three two-color LEDs on its front panel. From left to right, the LEDs provide Link 1
status, Link 2 status, and module health status, respectively. The following table
summarizes some typical indications for reference.
4-Character
Link 1 Status LED
If Module Health
LED is . . .
Flashing Red/Green
Flashing Red/Off
Flashing Green/Off
or Solid Green
Flashing Green/Off
348
Experion PKS Series A Fieldbus Interface Module User's Guide
1 - 1
0
Display
Link 2 Status LED

Figure 33 FIM front panel indicators.

Table 1 CIOM-AFIM LED Interpretations

And, 4-Character
Display shows . . .
TEST
LOAD
BOOT
ALIV
Honeywell
Module Health LED
Then, FIM is . . .
Running its self-test.
In the midst of a firmware load sequence.
Initiating its startup or boot sequence.
in its ALIVE state and ready for its Personality
Image load.