Step
7
Press <Tab>.
TIP
The following illustration shows the entry fields that are common for time related
values. The values shown are the maximums for the given field. Use the Left and
Right Arrow keys on the keyboard to move the cursor left or right in the field and use
the increase and decrease buttons provided to adjust values in the selected field.
8
Accept default value for Step Time
Preset (T1) parameter or key in a new
value. This is the preset value for the
System Management step timer. The
default value is 15. 0000s. Press <Tab>.
9
Accept the default value for the Preset
Set Addr Seq Timer (T2) parameter or
key in a new value. This is the preset
value for the System Management set
address sequence timer. The default
value is 01:30. 0000s. Press <Tab>.
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
July 2010
5.4. Configuring Fieldbus Components In a Control Strategy
Action
Honeywell
Result
Moves cursor to the Step Timer Preset
(T1) field and highlights it.
Moves cursor to the Preset Set Addr Seq
Timer (T2) field and highlights it.
Moves cursor to the Preset Set Addr Wait
Timer (T3) field and highlights it.
5. Configuration
137