ATTENTION
If you use a version 4.02.02 or older Honeywell Fieldbus device or a
version 2.02.02 or older FlowServe Fieldbus device as a backup Link
Master node with redundant CIOM-A FIMs, we recommend that you
assign the device to address 40 (decimal).
Do not assign addresses below 30 to any backup Link Master devices
If Control Module
FFPERIOD Is . . .
250 milliseconds
500 milliseconds
1 second
2 seconds
4 seconds

Adding CIOM-A FIM block to Project

Use the following procedure to add a CIOM-A Fieldbus Interface Module (FIM) block to
the Project tab in Control Builder. This also adds two Link blocks for the two H1 fieldbus
links that can be associated with this FIM. This procedure assumes the Control Builder
application is running.
TIP
You can configure a CIOM-A FIM block in the Control Builder Project tab
without the CIOM-A FIM hardware being installed. However, it is good idea to
have the communications driver and hardware that is going to be used for the
system installed, configured, and running. The CIOM-A FIM needs the name
of the communications driver specified on its configuration form to complete
its configuration data. Like the C200 CPM, the CIOM-A FIM represents a
hardware module and the block configuration specifies the communication
path to the hardware.
Step
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
July 2010
5.4. Configuring Fieldbus Components In a Control Strategy
Then, Be Sure
STALECOUNT Value
Is at Least . . .
4
3
3
3
3
Action
Honeywell
And, Device Resource Block SHED_RCAS
and SHED_ROUT Values Are at Least . . .
5 seconds
5 seconds
5 seconds
5 seconds
5 seconds
Result
5. Configuration