Step
7
Click Yes.
8
Click the
Status field.
9
For this example, select Good from the
menu.
10
Click Yes.
11
Press <Tab>.
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
July 2010
Action
button in the Simulate
Honeywell
8. Maintenance, Checkout, and Calibration
8.7. Using Fieldbus Device Simulate Function
Result
Initiates the simulate function. Check that
the Simulation Active button is ON in the
Block Errors (Blk Alarm) list on the form.
Opens drop-down menu.
Opens Change Online Value
confirmation dialog.
Sets Simulate Status to Good.
Moves cursor to the Simulate Value field.
339