Step
7
Click
button to select slot number
where CIOM-A FIM is installed from
dropdown list. Use slot 05 for this
example. Press <Tab>.
(Remember that chassis slot numbering
is zero-based from left to right.)
8
If CIOM-A FIM is located in a Remote I/O
Chassis, click this box to select it.
Otherwise, skip this Step, press <Tab>,
and go to the Result column in Step 12.
Skip the step for this example.
9
Click
button to select address of the
ControlNet Network module in the
Supervisory chassis that is connected to
the ControlNet Network module (Uplink)
in the Remote I/O Chassis. Use 04 for
this example. Press <Tab>.
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
July 2010
5.4. Configuring Fieldbus Components In a Control Strategy
Action
Honeywell
Result
Moves cursor to the Remote Chassis
checkbox .
Enables Remote Chassis selection fields.
Moves cursor to DownLink Slot Number
entry field and highlights it.
5. Configuration