10.2 Standard Function Blocks

WARNING
The Fieldbus Foundation specifications do not clearly state the expectations
of fieldbus devices for handling Not-a-Number (NaN) values. This means that
some may behave as the user desires and others may not.
If you compute a data type float + status value that uses data structure (DS-
65), which includes all F
contained parameters, a resulting NaN value passed outbound through the
FIM sets the status element to BAD and changes the value element from
NaN to 0.0 (zero). If you compute a data type float value, which includes
many contained values such as alarm trip points, set points or output limits,
gains, and filter time values, a resulting NaN value that is to be passed
outbound through the FIM will not be written and usually results in retention of
R400