3. Fieldbus Integration With Experion System
3.6. Notification Scheme
notification system. The following table summarizes the possible fieldbus alarm
enumerations and lists the alarm/event type identification to be used in the alarm
summary and event summary displays in Station.
ATTENTION
Only the first alarm in an overlapping series of alarms associated with
BLOCK_ERR and XD_ERROR bitstring alarms is reported due to a flaw in
the Fieldbus Foundation Specifications regarding the alert state machine.
This has been reported to the Fieldbus Foundation through their Action
Request system and the Foundation has agreed to permit future devices to
issue alerts on changes to the status of any element of these bitstring alarms.
If no more than one of the bits is set at a time, the alarms are reported and
cleared properly
TIP
Fieldbus alarm functions do not support rate of change (ROC) alarms. ROC
alarms can only be generated in applications that use Control Builder Data
Acquisition blocks for input signal conditioning.
Enumeration
UNDEF
LO
HI
LO LO
HI HI
DV LO
DV HI
DISC
DISC
DISC
74
Experion PKS Series A Fieldbus Interface Module User's Guide
Description
Undefended Alarm
Low Limit Alarm
High Limit Alarm
Critical Low Limit Alarm
Critical High Limit Alarm
Deviation Low Alarm
Deviation High Alarm
Standard Discrete Alarm
Standard Discrete Alarm
DevCtl Fail Alarm
Honeywell
Alarm/Event Type
No Action
PVLO
PVHI
PVLOLO
PVHIHI
DEVLO
DEVHI
OFFNORM
CHNGOFST
FBDCFAIL
R400
July 2010