6. Operation
6.3. Monitoring Fieldbus Functions Through Monitoring Tab
Step
TIP
You can also initiate a Link shutdown through the SEG Command field on the Link
Parameters form in Monitoring. Just click Edit->Configure Module Properties to call up
the Link Block Parameters form, select SHUTDOWN from the dropdown menu for the
SEG Command field, and click Yes to acknowledge the action. You can also confirm
the current state of the link through the SEG State field. (Note that all associated
fieldbus device blocks are also shutdown, including those contained in Control
Modules.)
2
Click the Yes button.
254
Experion PKS Series A Fieldbus Interface Module User's Guide
Action
Honeywell
Result
Initiates state change. The LINK icon
changes from green to blue. This
illustration is for example purposes only.
The CIOM-A FIM is only inactivated
when both Links are inactivated.
R400