Honeywell Series A User Manual page 549

Fieldbus interface module
Hide thumbs Also See for Series A:
Table of Contents

Advertisement

Tab
Post Trans Gap
Extension
(LMLSTREC.PTGEXT
N)
Max Inter Channel
Signal Skew
(LMLSTREC.MXICSS
W)
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
July 2010
Parameter
Default Value
0
0
Honeywell
18. Appendix I
18.2. Description
Description
Specifies an extension to the
minimum period during which a
subsequent transmission shall
not commence after
transmission of a PhPDU. For
the same minimum period after
reception of a PhPDU, the
receiving Physical Layer entity
shall ignore all received
signaling. A Medium Dependent
Sublayer (MDS) entity shall set
a minimum post transmission
period of four nominal bit times.
The period may be extended,
but not reduced. It is an
Unsigned8 variable with
allowable values between 0 and
7.
Defines the maximum accepted
differential delay between any
two active channels, as
measured from the first PhPDU
of a start delimiter, if the device
is to receive concurrently on
more than one channel. The
delay shall not exceed five
nominal bit times. This period
may be extended, but not
reduced. The value of the post
transmission gap shall be
greater than the value of inter
channel skew. It is an
Unsigned8 variable with
allowable values between 0 and
7.
549