16. Appendix G
16.1. Loading CIOM-A FIM firmware
Step
3
Click the OK button to acknowledge the
message prompt.
Click the Resume button
toolbar.
4
Click the node icon.
522
Experion PKS Series A Fieldbus Interface Module User's Guide
Action
in the
Honeywell
Result
Ntools begins scanning the network for
installed components. Detected nodes
will appear under the Desktop directory.
This illustration is for example purposes
only.
If this is the first time Ntools has been
used on the system, the Settings dialog
box opens. Otherwise, see the next
Result row and skip to Step 6.
R400
July 2010