Alert_Key - Honeywell Series A User Manual

Fieldbus interface module
Hide thumbs Also See for Series A:
Table of Contents

Advertisement

11. Appendix B
11.1. Standard Function Block Parameters
Classification
Description
FF Data Type
Range
Usage
Length
Valid Views
Storage
Remarks

ALERT_KEY

Classification
Description
FF Data Type
Range
Usage
Length
Valid Views
Storage
Remarks
420
Experion PKS Series A Fieldbus Interface Module User's Guide
Record
Detects the current alert status, unacknowledged states,
and disable states of the alarms associated with the block
DS-74
C/Alarm Summary
8
VIEW_1, VIEW_3
Dynamic
The data type summarizes 16 alerts using the following 4
elements.
1 Current
2 Unacknowledged
3 Unreported
4 Disabled
Simple Variable
The identification number of the plant unit. This data may
be used in the host for sorting alarms.
Unsigned 8
1 to 255
C/Alert Key
1
VIEW_4
Static
Initial value is 0
Honeywell
R400
July 2010

Advertisement

Table of Contents
loading

This manual is also suitable for:

Experion pks series a

Table of Contents