11. Appendix B
11.1. Standard Function Block Parameters

SP_RATE-UP

Classification
Description
FF Data Type
Range
Usage
Length
Valid Views
Storage
Remarks

ST_REV

Classification
Description
FF Data Type
Range
Usage
Length
Valid Views
Storage
Remarks

STATUS_OPTS

Classification
484
Experion PKS Series A Fieldbus Interface Module User's Guide
Simple Variable
Defines the upward ramp rate in PV units per second for
set point changes to invoke action in the Auto mode.
Float
Positive
C/Contained
4
VIEW_4
Static
If the ramp rate is set to zero or the block is not in Auto
mode, the set point change is invoked immediately.
Simple Variable
Defines the revision level of the static data associated with
the function block. The revision value is incremented each
time a static parameter value in the block is changed.
Unsigned 16
C/Static Revision
2
VIEW_1, VIEW_2, VIEW_3, VIEW_4
Static
Read Only
Simple Variable
Honeywell
R400
July 2010