4. Installation
4.3. Installing Fieldbus RTP TC-FFRU01/TC-FFRP02 or RRTP TC-FFSU01/TC-FFSP02
Hole Size:
0.156
3.96
4.75
120.7

Wiring

WARNING
Use only Fieldbus approved components with the RTP, so the intrinsically
safe values of the bus system are not exceeded.
Do not use the RTP in an intrinsically safe environment after it has been
exposed to non-intrinsically safe signals.
ATTENTION
The power requirement for the TC-FFRP02 is 24 Vdc at 270 mA.
Use the following procedure to make wiring connections to the RTP.
112
Experion PKS Series A Fieldbus Interface Module User's Guide
6.98
177.3
J1
SEGMENT
#1
J5
1
J6
7.5
190.5
Models TC-FFSU01 and TC-FFSP02
Honeywell
J2
SEGMENT
#2
J7
1
J8
0.425
10.8
4.10
104.2
0.225
5.7
R400
July 2010