11. Appendix B
11.1. Standard Function Block Parameters
Description
FF Data Type
Range
Usage
Length
Valid Views
Storage
Remarks

LO_ALM

Classification
Description
FF Data Type
Range
Usage
Length
Valid Views
Storage
454
Experion PKS Series A Fieldbus Interface Module User's Guide
Determines whether the values passed by the Transducer
block to the Analog Input block may be used directly
(DIRECT) or, if the value is in different units, must be
converted linearly (indirectly); or with square root (Ind Sqr
Root), using the input range defined by the transducer and
associated output range.
Unsigned 8
1: Direct
2: Indirect
3: Ind Sqr Root
C/Contained
1
VIEW_4
Static
Record
Represents the status of the low alarm and its associated
time stamp.
DS-71
C/Alarm
16
Dynamic
Honeywell
R400
July 2010